This document is the electronic engine governor controller user manual, which introduces the function and features of the electronic engine governor controller, including engine start smoke limiting function, idle speed setting, ramp time setting, etc.
This manual provides detailed instructions for installing and adjusting the EG3002F electronic engine governor controller. It covers wiring connections, potentiometer adjustments, DIP switch configurations, and troubleshooting for engines with external, built-in, or PT-Pump actuators. The controller supports frequency ranges from 600 to 9500 Hz and includes features like idle speed control, ramp time adjustment, and speed droop for parallel operation.
The manual also explains how to configure the unit for Cummins PT-Pump engines and "extreme slow response" engines, with specific settings for gain, integral, and differential parameters. Safety warnings are included, such as the absence of over-speed protection and the need for a separate over-speed device. Installation must be performed by qualified personnel using shielded cables and proper wire gauges.
| Output Voltage | Max. 95% of Input Voltage |
|---|---|
| Current Continuous | 7A min. 0.5A Max. 15A 10 seconds |
| Operating Temperature | -40 to +80 ˚C |
| Storage Temperature | -40 to +85 ˚C |
| Ramp Time | 3 − 20 seconds (adjustable) |
Adjust the IDLE Speed potentiometer when terminals 2 & 3 are shorted.
A speed droop of 2% at maximum load is recommended.