This document is a calibration manual for Digi-Sense® TC9100 and TC9600 Advanced Temperature Controllers. It explains how to calibrate the temperature controller and provides the range of calibration temperature points.
This manual details how to calibrate Digi-Sense TC9100 and TC9600 temperature controllers using built-in calibration gateways. It covers full-range and segmented calibration methods for various sensor types including thermocouples, platinum RTDs, and thermistors. Each unit comes with preloaded default calibration points for accurate readings across the full temperature range.
Calibration requires specific equipment such as a Fluke 753 or equivalent for thermocouples and RTDs, and an IET decade box for thermistors. The process involves setting six temperature points, confirming calibration, and saving or discarding changes.
| Calibration Points | Six temperature points |
|---|---|
| Thermocouple Accuracy | +/-0.1% of span or +/-oC for types J, K, T, E, N; +/- 0.2% of span or +/-2oC for types B,R,S |
| Platinum RTD Accuracy | +/-0.1% of span |
| Thermistor Accuracy | +/-0.4% of span or +/-0.5oC |
Fluke 753 or equivalent for thermocouples and RTDs, and an IET decade box for thermistors.
Six temperature points can be set for calibration.
Default points vary by type: e.g., Type J: -185, -85, 0, 230, 660, 995 °C.
Yes, but it is not recommended for full-range calibration due to nonlinearity of temperature probes.