Fisher 3710 and 3720 Valve Positioners and 3722 Electro-Pneumatic Converter Instruction Manual

This document introduces the functions and characteristics of 3710 and 3720 valve positioners and 3722 electro-pneumatic converters, and the installation methods.


Fisher 3710 and 3720 Valve Positioners and 3722 Electro-Pneumatic Converter Instruction Manual - cover page
Brand
Fisher
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
52
File format
PDF
File size
883 KB
Published
17 October, 2023
Updated
17 October, 2023
MD5 checksum
CC96E69D97C1F8C2545166BE012DE4A8

About this manual

The manual covers installation, operation, calibration, maintenance, and parts ordering for Fisher 3710 pneumatic and 3720 electro-pneumatic valve positioners. It also provides field installation and maintenance information for the Fisher 3722 electro-pneumatic converter.

The 3710 accepts a pneumatic input signal and the 3720 accepts a milliampere direct current input signal. The positioners can be configured for single- or double-acting output and for direct or reverse action, and the manual includes connections, calibration adjustments, specifications, and parts lists.

What's inside

  • Introduction
  • Specifications
  • Installing the 3722 Converter
  • Installation
  • Connections
  • Calibration
  • Principle of Operation
  • Maintenance
  • Parts Ordering
  • Parts List

Specifications

Input Signal (3710)Standard: 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig); split-range available
Input Signal (3720)4-20 mA DC constant current with 30 VDC maximum compliance voltage; split-range 4-12 mA DC or 12-20 mA DC
Output SignalPneumatic pressure as required by the actuator up to full supply pressure
Supply PressureRecommended 0.3 bar (5 psig) above actuator requirement; maximum 10.3 bar (150 psig) or the actuator maximum pressure rating, whichever is lower
Supply Medium3710: Air or Natural Gas; 3720: Air
Pressure Connections1/4 NPT internal
Electrical Connection for 37201/2-14 NPT conduit connection
Approximate Weight3710: 2.04 kg (4.5 pounds); 3720: 2.72 kg (6.0 pounds)

Frequently asked questions

What input signal does the Fisher 3710 positioner accept?

The 3710 accepts a standard pneumatic input of 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig); it can also be split-ranged.

What input signal does the Fisher 3720 positioner accept?

The 3720 accepts a 4-20 mA DC constant current input with a 30 VDC maximum compliance voltage; split-range versions use 4-12 mA DC or 12-20 mA DC.

What does the Fisher 3722 electro-pneumatic converter do?

It converts a 4-20 mA DC input signal to a 0.2 to 1.0 bar (3 to 15 psig) signal for the pneumatic positioner.

Can the 3720 positioner use natural gas as its supply medium?

No. The manual states that 3720 positioners are not approved for use with natural gas as the supply medium; the 3710 can use air or natural gas.