64 及 67C Series Regulators Manual, introduces the features and characteristics of the series regulators, including product models, export pressure range, etc.
This document serves as a guide for the installation, operation, and maintenance of Fisher 64 and 67C series regulators. These direct-acting regulators are designed for high-pressure applications involving liquefied petroleum gas (LPG), natural gas, and air vapor applications, as well as liquid LPG applications. The manual covers various models including the 64, 64KB, 64SR, 67CW, 67CH, 67CD, and 67CN types, detailing their specific features and pressure ranges. This manual is written in Chinese.
| Body Size, Inlet and Outlet Connections | 64 Series: 1/2 inch NPT; 67C Series: 1/4 inch NPT |
|---|---|
| Maximum Inlet Pressure | 250 psig (17.2 bar) |
| Maximum Emergency Outlet Pressure | 64 Series: 220 psig; 67C Series: Outlet Pressure + 50 psig |
| Temperature Range | 64 Series: -20°F to 150°F; 67C Series: -20°F to 180°F |
| Weight | 64 Series: 2.25 lbs; 67C Series: 1 lb |
Only the 64KB model is suitable for ammonia water conditions, as other models contain brass materials incompatible with ammonia water.
No, the 67CN model is set at the factory and cannot be adjusted on-site.
The regulator should be installed at least 18 inches (45 cm) above the ground to prevent rain splash from freezing in the vent opening.