Fisher 846 Electro-Pneumatic Transducer Installation and Maintenance Manual

This document is the data manual for Fisher™ 846 solenoid valve, which mainly introduces the characteristics, installation and use methods of the solenoid valve.


Fisher 846 Electro-Pneumatic Transducer Installation and Maintenance Manual - cover page
Brand
Fisher
Category
Industrial Supply
Document type
User Manual
Language
Spanish
Pages
44
File format
PDF
File size
555 KB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
30670884B486DD1EF473BF5503BB2645

About this manual

The Fisher 846 is an electronic I/P transducer that accepts an electrical input signal and produces a proportional pneumatic output. It is designed to operate control valve actuators or positioners and can also generate signals for pneumatic receiving instruments. The device features a single electronic circuit board and a replaceable end module containing the pilot/actuator assembly and amplifier stage, which minimizes repair time. This manual is written in Spanish.

What's inside

  • Introduction
  • Specifications
  • Installation
  • Mounting
  • Pressure Connections
  • Electrical Connections
  • Calibration
  • Operation
  • Troubleshooting
  • Maintenance

Specifications

Input Signal4 to 20 mA DC, 4 to 12 mA DC, or 12 to 20 mA DC
Output Signal (Direct Action)0.2 to 1.0 bar (3 to 15 psi)
Supply Pressure (Standard)1.2 to 1.6 bar (18 to 24 psi)
Operating Temperature-40 to 85 °C (-40 to 185 °F)
Accuracy±0.30% of output span
Linearity, Hysteresis, and Repeatability±0.3% of span
Air Supply Capacity (Standard)6.4 m3/hr (240 scfh)
Electrical Connection1/2 - 14 NPT conduit connection

Frequently asked questions

What is the typical output range for direct action?

The typical output range for direct action is 0.2 to 1.0 bar (3 to 15 psi).

What is the maximum supply pressure?

The maximum supply pressure is 2.4 bar (35 psi).

Is the Fisher 846 intrinsically safe?

Yes, it is certified as intrinsically safe by cCSAus, FM, ATEX, IECEx, and other agencies.

What is the accuracy of the transducer?

The accuracy is ±0.30% of the output span.