This document is the data manual for Fisher™ 846 solenoid valve, which mainly introduces the characteristics, installation and use methods of the solenoid valve.
The Fisher 846 is an electronic I/P transducer that accepts an electrical input signal and produces a proportional pneumatic output. It is designed to operate control valve actuators or positioners and can also generate signals for pneumatic receiving instruments. The device features a single electronic circuit board and a replaceable end module containing the pilot/actuator assembly and amplifier stage, which minimizes repair time. This manual is written in Spanish.
| Input Signal | 4 to 20 mA DC, 4 to 12 mA DC, or 12 to 20 mA DC |
|---|---|
| Output Signal (Direct Action) | 0.2 to 1.0 bar (3 to 15 psi) |
| Supply Pressure (Standard) | 1.2 to 1.6 bar (18 to 24 psi) |
| Operating Temperature | -40 to 85 °C (-40 to 185 °F) |
| Accuracy | ±0.30% of output span |
| Linearity, Hysteresis, and Repeatability | ±0.3% of span |
| Air Supply Capacity (Standard) | 6.4 m3/hr (240 scfh) |
| Electrical Connection | 1/2 - 14 NPT conduit connection |
The typical output range for direct action is 0.2 to 1.0 bar (3 to 15 psi).
The maximum supply pressure is 2.4 bar (35 psi).
Yes, it is certified as intrinsically safe by cCSAus, FM, ATEX, IECEx, and other agencies.
The accuracy is ±0.30% of the output span.