fisher 2502 controller user manual, introduces the features and installation and debugging methods of the controller
The Fisher 2502 controller is a pneumatic device designed to control liquid level, interface levels, or density when used in combination with Fisher 249 liquid level sensors. It provides proportional-plus-reset and proportional-plus-reset with differential relief valve control, with an output signal that operates a final control element. The unit is available in various configurations, including direct-acting (2502), with a level indicator (2502C), and with a differential relief valve (2502F), and can be ordered with reverse action.
| Input Signal | Liquid Level or Liquid-to-Liquid Interface Level: From 0 to 100 percent of displacer length |
|---|---|
| Output Signal | 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig) |
| Supply Pressure Requirement | 1.4 bar (20 psig) for 0.2 to 1.0 bar output signal |
| Maximum Supply Pressure | 3.4 bar (50 psig) |
| Hysteresis | 0.6 percent of output pressure change at 100 percent of proportional band |
| Dead Band | 0.05 percent of proportional band or span |
| Reset Adjustment Range | Adjustable from 0.01 to 74 minutes per repeat |
The supply pressure requirement is 1.4 bar (20 psig).
The maximum supply pressure is 3.4 bar (50 psig).
Yes, the action is field reversible between direct and reverse.