Fisher 133 Series Gas Regulator Service Manual

Service manual for Fisher 133 series gas regulators covering specifications, installation, adjustment, maintenance and parts ordering.


Fisher 133 Series Gas Regulator Service Manual - cover page
Brand
Fisher
Document type
Service Manual
Language
Chinese
Pages
16
File format
PDF
File size
2.4 MB
Published
08 October, 2026
Updated
08 October, 2026
MD5 checksum
858D866208DFCA94C9179B7661356643

About this manual

The Fisher 133 series gas regulator service manual provides detailed information on the specifications, operation principle, installation, over‑pressure protection, startup, adjustment, shutdown, maintenance and parts ordering for the 133H, 133L, 133Z and 133HP models. It is intended for qualified personnel who have received training or have sufficient experience with the equipment.

The manual includes safety warnings, required downstream control line dimensions, exhaust port protection, and step‑by‑step procedures for disassembly, inspection, replacement of seals, diaphragms, springs and other components, as well as re‑assembly instructions and torque specifications. This manual is written in Chinese.

What's inside

  • Overview
  • Specifications
  • Working Principle
  • Installation
  • Over‑pressure Protection
  • Startup
  • Adjustment
  • Shutdown
  • Maintenance
  • Parts List

Specifications

Operating temperature range-29 to 66 °C
Maximum working inlet pressure (133H/133L/133Z)4.1 bar / 60 psig
Maximum emergency inlet pressure (all models)8.6 bar / 125 psig
Maximum outlet pressure (133H/133L/133Z)0.69 bar / 10 psig
Maximum outlet pressure (133HP)4.1 bar / 60 psig
Weight (NPT end‑connection)16 kg (35 lb) for 133H/133L/133Z
Weight (flanged end‑connection)18 kg (40 lb) for 133H/133L/133Z
Downstream control line minimum diameter12.7 mm (1/2 in)
Exhaust port connection (133H/133L/133Z)1 NPT (internal) with filter
Exhaust port connection (133HP)1/2 NPT (internal) with Fisher Y602‑7 exhaust component

Frequently asked questions

What size downstream control line is required for the 133 series regulator?

The downstream control line must be at least 12.7 mm (1/2 in) in diameter and installed 5 to 10 times the pipe diameter downstream of the regulator.

What is the maximum operating temperature for the 133 series regulator?

The regulator can operate from –29 °C up to 66 °C (–20 °F to 150 °F).

What is the maximum working inlet pressure for the 133H model?

The maximum working inlet pressure for the 133H model is 4.1 bar (60 psig).

Download PDF (2.4 MB)