This manual describes the steps for installing and configuring the VACON® NX CANopen board. The manual also describes the CANopen protocol and how to use VACON® NX drives for CANopen communication.
The Vacon NX OPTC6 is a fieldbus board designed to connect Vacon NX AC drives to a CANopen system. It allows the drive to be controlled, monitored, and programmed from a host system via standard CANopen profiles (CiA DS-301). The board installs in slot D or E on the control board of the AC drive.
| Interface Connector Type | Open Style Connector (Pluggable connector, 5.08mm) |
|---|---|
| Transfer Cable Type | 2wire twisted shielded cable |
| Electrical Isolation | 500 VDC |
| Communication Standard | CANopen CiA DS-301, GiA DSP-402 |
| Address Range | 1 - 127 |
The CANopen fieldbus board is installed in slot D or slot E on the control board of the AC drive.
Cables should have a nominal impedance of 120 Ohm and a specific line delay of nominal 5 ns/m.
If the Vacon drive is the last device on the line, set jumper X6 to ON or connect an external 120 Ohm resistor between terminals 2 and 4.