This manual provides detailed information about the functions and use of the vacon®20 x ac drive optbk as-interface option board.
The Vacon OPTBK AS-Interface option board allows Vacon frequency converters to connect to the AS-i (Actuator Sensor Interface) bus system. This interface is designed for the lower field level to network binary sensors and actuators economically and reliably. The board supports a flexible topology and uses a simple, rugged cable system that reduces installation errors and downtime.
| AS-Interface profile | S-7.A.7 (AS-i specifications 3.0) |
|---|---|
| Network type | Line, Bus, Star or Tree Topology |
| Max. current consumption | 150 mA |
| Data Rate | 167 kBit/s |
| Max. Stations | 1 Master and up to 62 Slaves |
| Data per Slave | 4 bit digital Input and 4 bit digital Output |
| Power supply voltage | 29.5 to 31.6 volts DC |
No, the AS-interface negative (ASI N) cannot be grounded because the two wires carry both power and signal.
A segment can be up to 100m long, extendible up to 300m with Repeaters.
No, it is not allowed to add or replace option boards on a frequency converter with the power switched on.