This document is the user manual of Danfoss / Vacon NXS 0045 5 B 2 H 1 SSS, which mainly introduces the board types, technical data and hardware protections of the product.
The document provides a comprehensive guide to the Vacon NX range of expander and adapter boards, specifically detailing their use with the NXS and NXP frequency converter types. It explains how these modular boards increase input/output versatility by connecting to specific slots on the control board.
Detailed sections cover technical data for all inputs and outputs, including analogue voltage/current ranges, digital signal levels, relay capacities, and environmental specifications. The manual also categorizes boards into Basic (OPTA_), Expander (OPTB_), Fieldbus (OPTC_), and Adapter (OPTD_) types.
| Analogue inputs (voltage) | 0…±10V, Ri ≥ 200 kΩ |
|---|---|
| Analogue inputs (current) | 0(4)…20mA, Ri = 250Ω |
| Digital inputs (DC) | 24V: "0"≤10V, "1"≥18V |
| Auxiliary voltage output (+24V) | 24V (±15%), max 250mA |
| Ambient operating temperature | -10…55°C |
The I/O boards are usually interchangeable between different Vacon types, i.e. NXS and NXP.
The boards are divided into Basic (OPTA_), Expander (OPTB_), Fieldbus (OPTC_), and Adapter (OPTD_) groups.
The maximum load on the +24V/EXT+24V output per board is 150mA.