About this manual

The document provides a comprehensive guide to the Vacon NX range of expander and adapter boards, specifically detailing their use with the NXS and NXP frequency converter types. It explains how these modular boards increase input/output versatility by connecting to specific slots on the control board.

Detailed sections cover technical data for all inputs and outputs, including analogue voltage/current ranges, digital signal levels, relay capacities, and environmental specifications. The manual also categorizes boards into Basic (OPTA_), Expander (OPTB_), Fieldbus (OPTC_), and Adapter (OPTD_) types.

What's inside

  • General information
  • Board slots on the control board
  • Option board types
  • Technical data
  • Hardware protections
  • Installation of Vacon Option Boards
  • Descriptions of Basic boards OPTA_
  • Descriptions of I/O Expander Boards OPTB_
  • Descriptions of Adapter Boards OPTD_

Specifications

Analogue inputs (voltage)0…±10V, Ri ≥ 200 kΩ
Analogue inputs (current)0(4)…20mA, Ri = 250Ω
Digital inputs (DC)24V: "0"≤10V, "1"≥18V
Auxiliary voltage output (+24V)24V (±15%), max 250mA
Ambient operating temperature-10…55°C

Frequently asked questions

Which Vacon types are compatible with these option boards?

The I/O boards are usually interchangeable between different Vacon types, i.e. NXS and NXP.

What are the four groups of Vacon option board types?

The boards are divided into Basic (OPTA_), Expander (OPTB_), Fieldbus (OPTC_), and Adapter (OPTD_) groups.

What is the maximum load on the +24V output per board?

The maximum load on the +24V/EXT+24V output per board is 150mA.