vacon nx ac drives optc6 canopen option board user manual. This document introduces the technical data, installation, and usage of vacon nx ac drives optc6 canopen option board.
The Vacon OPTC6 is a fieldbus board designed to connect Vacon NX frequency converters to a CanOpen system. It allows the drive to be controlled, monitored, and programmed from an external host system via the Controller Area Network (CAN) protocol.
Installation requires placing the board in slot E on the control board of the frequency converter. The manual details physical connections, including grounding methods for the bus cable shield and setting termination resistors if the drive is the last device on the line. It also explains LED status indicators for both the option board and fieldbus module.
| Interface Connector Type | Pluggable connector, 5.08mm |
|---|---|
| Data Transfer Method | CAN [ISO 11898] |
| Electrical Isolation | 500 VDC |
| Communication Standard | CanOpen CiA DS-301 |
| Address Range | 1-127 |
The fieldbus board shall be installed in slot E on the control board of the frequency converter.
Bus termination must be set using jumper X1 (ON position) or an external 120Ω resistor connected to terminals 2 and 4.
It indicates that the option board is activated but in a FAULT state.