R122H, R222H, R222, R232A and R232E Series LP-Gas Regulators, this manual provides information on how to properly install and maintain the regulators.
This manual covers the installation and maintenance procedures for the Fisher R122H, R222H, R222, R232A, and R232E series LP-Gas regulators. These devices are designed for vapor service applications and include first stage, second stage, and integral two-stage configurations. The document emphasizes that these regulators must not be used on liquid service and provides specific safety warnings regarding indoor installation and venting requirements.
| Maximum Allowable Inlet Pressure | 250 psig / 17.2 bar |
|---|---|
| Temperature Capabilities | -20 to 160°F / -29 to 71°C |
| Outlet Pressure Standard Setpoint | 10 psi / 0.69 bar or 5 psi / 0.35 bar |
No, they are not to be used on liquid service.
No, they are not suitable for indoor installations.
The regulator should be installed with the vent pointed vertically down.