This manual provides instructions for the maintenance and installation of low-pressure regulators.
This instruction manual covers the installation and maintenance of Fisher single and second-stage LP-gas regulators, specifically Types 912, R322, R352, R722, R922, R932, and $102L. The document details the scope of the manual, describes the physical characteristics of the regulators, and lists their technical specifications.
| Outlet Pressure Setting | 11-inches w.c (27 mbar) |
|---|---|
| Temperature Limits | -20° to 160° F (-29° to 71° C) |
| Maximum Inlet Pressure (Second-Stage) | 20 psig (1,4 bar) |
| Minimum Ground Clearance | 18-inches (457 mm) |
This manual covers single and second-stage LP-gas regulators, including Types 912, R322, R352, R722, R922, R932, and $102L.
To increase pressure, remove the closing cap and turn the adjusting screw clockwise; to decrease, turn it counterclockwise.
The vent discharge must be at least 3 feet horizontally from any building opening below the level of the discharge.