This document is a quick guide for VLT® AutomationDrive FC 360 frequency converter, which provides information on installation, commissioning, applications, diagnostics, and troubleshooting of the product.
This document serves as a quick guide for the safe installation and commissioning of the Danfoss VLT AutomationDrive FC 360 variable frequency drive. It is intended for qualified personnel and covers essential topics including product overview, safety instructions, mechanical and electrical installation, commissioning procedures, applications, and troubleshooting. This manual is written in Chinese.
| Power Range | 0.37–75 kW (0.5–100 hp) |
|---|---|
| Discharge Time (0.37–7.5 kW) | 4 minutes |
| Discharge Time (11–75 kW) | 15 minutes |
The minimum discharge time is 4 minutes after disconnection.
The device presents a shock hazard if the leakage current exceeds 3.5 mA and it is not properly grounded.
The drive accepts a three-phase AC main power input in the range of 380–480 V.