This manual provides installation, adjustment, configuration, maintenance, and troubleshooting instructions for the Yamatake SVP3000 Alphaplus intelligent…
This document is the user manual for the Yamatake SVP3000 Alphaplus intelligent valve positioners, specifically models AVP100 and AVP102. It covers essential safety precautions, unpacking, and storage requirements to ensure safe operation and longevity of the device. The manual details the installation process, including assembly of the feedback shaft, mounting steps, pneumatic supply requirements, and electrical wiring principles. This manual is written in Chinese.
| Input Signal Range | 4-20mA or HART signal |
|---|---|
| Output Signal | 4-20mA |
| Operating Temperature (Ex ia IIC T4-T6) | -20°C to +60°C |
| Operating Temperature (Ex ia IIC T5) | -20°C to +60°C |
| Operating Temperature (Ex ia IIC T6) | -20°C to +40°C |
| Maximum Cable Capacitance | 0.06 µF |
| Maximum Cable Inductance | 1 mH |
The manual uses three types of safety instructions: Warning (potential danger leading to death or serious injury), Caution (potential danger leading to minor injury or equipment damage), and Note (useful information for the user).
The recommended air supply pipe should have an inner diameter of 6mm, preferably using piping with an outer diameter of 10mm.
The device supports manual communication, the Yamatake SFC160/260 field intelligent communicator, and the Emerson 275 HART communicator (for AVP102).
The air must be dry, with a dew point at least 10°C lower than the SVP's minimum ambient operating temperature.