STMicroelectronics AN307 Application Note

This article mainly introduces the phenomena that may occur in the circuit when controlling the AC power source using the triac, and how to avoid these phenomena by controlling the trigger mode of the triac to ensure the normal operation of the circuit.


STMicroelectronics AN307 Application Note - cover page
Brand
STMicroelectronics
Category
Other Electronics
Document type
Application Note
Language
English
Pages
9
File format
PDF
File size
56 KB
Published
06 August, 2012
Updated
30 September, 2023
Model
AN307
MD5 checksum
E6D7F893D28874EE187C7BBFF3C1045E

About this manual

This document reviews the principles required for the correct operation of triacs when controlling inductive loads, such as motors or transformers. It highlights that operating conditions vary significantly depending on the control mode and synchronization of the firing signal.

The text details various gate control methods, including single pulses, pulse trains, and DC current, analyzing their impact on synchronization and load saturation. It specifically addresses transient phenomena during triggering, explaining how firing at zero mains voltage can cause high overloads due to magnetic saturation, whereas firing at peak voltage is generally safer. The note concludes with recommendations to avoid transient overloads by synchronizing control signals and selecting appropriate control types.

What's inside

  • Introduction
  • Firing Control Signal
  • Gate Current Control by Single Pulse
  • Gate Control by Pulse Train
  • Gate Control by DC Current
  • Transient Phenomena During Triggering
  • Firing at Zero Mains Voltage
  • Firing at Peak Mains Voltage
  • Spurious Firing
  • Conclusion

Frequently asked questions

What precautions are needed when using triacs on inductive loads?

Designers must analyze various control modes and synchronization principles to guarantee correct operation and avoid overloads.

Why should triacs not be fired at zero mains voltage?

Firing at zero voltage can cause the induction to reach saturation, producing the highest transient overloads.

Which firing method is recommended for loads that can be saturated?

Firing at peak mains voltage is simple, efficient, and should be adopted whenever possible for such loads.