Describes the installation and start-up instructions for the ABB NCAN-02 CANopen Adapter Module
The Installation and Start‑up Guide is intended for engineers and technicians who install, commission and operate the NCAN-02 CANopen Adapter Module with an ABB drive. It assumes basic knowledge of electrical wiring and drive operation.
The document covers safety warnings, mechanical mounting, electrical wiring, DIP‑switch and parameter settings, CANopen configuration, communication details, diagnostic LED indications, technical data, and ambient condition limits. Appendices list technical specifications, connector pin‑outs, and environmental requirements.
| Enclosure dimensions | 100 × 22.5 × 115 mm (H×W×D) |
|---|---|
| Protection rating | IP20 |
| Current consumption | 30 mA at 24 VDC |
| Maximum DDCS link length | 10 m |
| Transfer rate (DDCS link) | 4 Mbit/s |
| Operating temperature range | 0 to +50 °C |
The drive must be switched off, and the intermediate circuit capacitors must be allowed to discharge for at least 5 minutes before any work is performed. It is good practice to verify discharge with a voltage‑indicating instrument.
The module has a plastic enclosure measuring 100 × 22.5 × 115 mm (H×W×D) and is rated IP20.
The maximum allowed length for the DDCS link is 10 m.
The module can operate in ambient temperatures from 0 °C up to +50 °C.