Siemens ET200M Active Bus Backplane Configuration Guide

This document describes the hardware structure and configuration of ET200M as a distributed DP slave, as well as the implementation of features such as module hot-plugging and functioning as a redundant slave. It mainly involves the configuration of active bus backplane and soft redundancy functionality.


Siemens ET200M Active Bus Backplane Configuration Guide - cover page
Brand
Siemens
Category
Industrial Supply
Document type
Application Note
Language
Chinese
Pages
9
File format
PDF
File size
302 KB
Published
23 February, 2012
Updated
28 September, 2023
MD5 checksum
101F47368D0BC361DB9E2662F4FA4E01

About this manual

This document explains the regular and active-backplane hardware configurations for the Siemens ET200M distributed I/O station. It lists active backplane templates, backplane boards, interface modules, and accessories with their order numbers.

It also describes module hot swap in soft-redundancy systems, including the functions supported, the limitations when using an S7-300 master, and the S7-400 configuration needed for full hot-swap support. This manual is written in Chinese.

What's inside

  • ET200M composition and description
  • Regular configuration
  • Active backplane configuration
  • Module hot swap in soft redundancy
  • Hot-swap function definitions
  • S7-300 soft-redundancy limitations
  • S7-400 configuration
  • Active backplane order numbers
  • IM153 interface modules

Specifications

Active backplane template, 19 inch6ES7 195-1GA00-0XAO; up to 5 templates
Active backplane template, 530 mm6ES7 195-1GF30-0XAO; up to 5 templates
BM2X40 backplane board6ES7 195-7HB00-0XAO; for 2 modules of 40 cm
BM1X80 backplane board6ES7 195-7HC00-0XAO; for 1 module of 80 mm
Basic IM153-2 interface module6ES7 153-2AA02-0XAO

Frequently asked questions

What does the active bus backplane enable for ET200M?

It enables soft redundancy and module hot swap for the ET200M station.

Can an S7-300 master achieve all hot-swap functions?

No; it lacks functions 3 and 4, so an S7-400 master is required for all four functions.

What happens when a module is removed in soft redundancy with an S7-300 master?

The CPU does not stop, the SF, BUSF, and BF lights turn on, ET200M I/O is cleared to 0, and the master loses control; reinserting the module switches control to the backup CPU.

How many active backplane templates can be installed?

Up to five active backplane templates can be installed.