Delta EME-A22A Analog Extension Card Instruction Sheet

This document is an instruction sheet for the EME-A22A Analog Extension Card for the VFD-E Series. It provides information on installation, parameter settings, and specifications.


Delta EME-A22A Analog Extension Card Instruction Sheet - cover page
Brand
AELTA
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
449 KB
Published
06 February, 2012
Updated
28 September, 2023
MD5 checksum
05EC443A57440D06AF3BB4877A4DDCE7

About this manual

This instruction sheet provides the necessary steps to install the Delta EME‑A22A analog extension card on a VFD‑E series drive. It emphasizes that the drive must be powered off before mounting, the card should be fixed with the supplied screws, and torque values must be observed (2 kgf‑cm for the card, 5 kgf‑cm for terminals). Wiring guidelines include using shielded wires, keeping a minimum 15 cm separation from other control or power cables, and routing wires at 90° when crossing.

The document also lists the environmental limits, electrical characteristics, and safety notes. Operating temperature ranges from –10 °C to 50 °C, storage temperature from –20 °C to +60 °C, and humidity below 90 % RH. Electrical specs include a 0‑10 VDC input range, 12‑bit resolution, and recommended wire gauge of 14‑24 AWG. Safety recommendations cover the use of fuses, RC networks or varistors for inductive loads, and proper grounding of shielded cables. This manual is written in Chinese.

What's inside

  • Installation
  • Mounting and Screw Torque
  • Environmental Conditions
  • Electrical Specifications
  • Input/Output Details
  • Wiring Guidelines
  • Safety Notes

Specifications

Maximum Humidity< 90% RH (non‑condensing)
Card Screw TorqueMaximum 2 kgf‑cm
Terminal Screw TorqueMaximum 5 kgf‑cm
Recommended Wire Gauge14‑24 AWG (0.21‑0.5 mm²)
Input Voltage Range0 ~ 10 VDC
Input Impedance100 kΩ
Resolution12 bits
Output Voltage Range0 ~ 10 VDC
Output Impedance1 kΩ ~ 2 MΩ
Output Current Range0 ~ 20 mA DC

Frequently asked questions

What input voltage range does the card accept?

The input voltage range is 0 ~ 10 VDC.

What wire gauge should be used for connections?

Use 14‑24 AWG (approximately 0.21‑0.5 mm²) wire for the connections.