Error codeA.041
PG divider ratio setting does not meet the allowed range or conditions. The manual's first action is: “DB stop.”
- Model
- YASKAWA III series SGM/SGDS
- Display shows
- Frequency‑divider pulse output setting error (A.041)
- Type
- Error code
- Source
- Manual p. 289
What A.041 means
Frequency‑divider pulse output setting error p. 289
Common causes
- PG divider ratio setting (Pn212) does not meet the allowed range or conditions. p. 289
- Occurs when the control power is turned on. p. 289
What to do
- DB stop. p. 289
- The PG divider pulse set by Pn212 is out of range or violates conditions – set Pn212 to an appropriate value. p. 289
Before you service the product, read the safety instructions in the manual p. 292.
If A.041 is still not resolved
- Unless designated personnel, do not perform settings, disassembly, and repair. Otherwise there is danger of electric shock or injury. p. 6 “除非是指定的人员,否则不要进行设置、拆卸与修理。否则会有触电或导致受伤的危险。”
- Contact designated personnel for settings, disassembly, and repair to avoid electric shock or injury. p. 6 “除非是指定的人员,否则不要进行设置、拆卸与修理。否则会有触电或导致受伤的危险。”
This page summarises what the manufacturer’s manual says about A.041; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with YASKAWA. Found a mistake? Report an error.