TECO A510 Error PGO: PG Open‑Circuit

TECO A510 inverter · taken from the manufacturer’s manual, pages cited

Fault codePGO

PG Open‑Circuit means when the inverter is running, the PG pulse is not detected within the PG open‑circuit detection time, or if parameter 20‑25 = 0 or 1, the inverter shuts down. The manual's first action is: “Check PG wiring. Check PG power supply. Check PG wiring. Inspect motor operation mechanism.”

Model
TECO A510
Display shows
PG Open‑Circuit (PGO)
Type
Fault code
Source
Manual p. 250

What PGO means

PG Open‑Circuit p. 250

Common causes

  • When the inverter is running, the PG pulse is not detected within the PG open‑circuit detection time (parameter 20‑26). p. 250
  • If parameter 20‑25 = 0 or 1, the inverter shuts down. p. 250
  • When the inverter is running, the PG pulse is not detected within the PG open‑circuit detection time (parameter 20‑26). p. 250
  • If parameter 20‑25 = 0 or 1, the inverter shuts down. p. 250
  • This fault detection is only active in V/F+PG and SV control modes (00‑00 = 1, 3, or 4). p. 250

What to do

  1. Check PG wiring. Check PG power supply. Check PG wiring. Inspect motor operation mechanism. p. 250
  2. PG wiring is incorrect. PG has no power. PG cable is broken. Brake mechanism engaged. p. 250
  3. Check PG wiring. p. 250
  4. Check PG power supply. p. 250
  5. Brake mechanism activated. p. 250

Before you service the product, read the safety instructions in the manual p. 252.

If PGO is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact TECO service.

This page summarises what the manufacturer’s manual says about PGO; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with TECO. Found a mistake? Report an error.