TECO A510 Error GE: Communication Error

TECO A510 inverter · taken from the manufacturer’s manual, pages cited

Fault codeGE

Communication Error means Modbus communication error, no communication received for longer than parameter 09‑06, or if parameter 09‑07 = 0‑2, this fault protection is triggered. The manual's first action is: “Connection is broken or communication with the host has stopped. Check all connections and verify all client software configurations.”

Model
TECO A510
Display shows
Communication Error (GE)
Type
Fault code
Source
Manual p. 250

What GE means

Communication Error p. 250

Common causes

  • Modbus communication error: no communication received for longer than parameter 09‑06 (communication fault detection time). p. 250
  • If parameter 09‑07 = 0‑2, this fault protection is triggered. p. 250

What to do

  1. Connection is broken or communication with the host has stopped. Check all connections and verify all client software configurations. p. 250

Before you service the product, read the safety instructions in the manual p. 252.

If GE is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact TECO service.