Code 09 indicates other auto-tuning errors excluding ATE-01 to ATE-08 errors such as no-load current exceeding 70%, rated current or torque exceeding reference 100%, or incorrect relationship between motor output current and motor rated current. The manual's first action is: “Check motor connection wires.”
- Model
- TECO A510
- Display shows
- Other auto‑tuning errors (09)
- Type
- Error code
- Source
- Manual p. 257
What 09 means
Other auto‑tuning errors p. 257
Common causes
- Other auto‑tuning errors (excluding ATE‑01 to ATE‑08 errors, e.g., no‑load current >70 %, rated current or torque exceeds reference 100 %). p. 257
- Incorrect relationship between motor output current and motor rated current. p. 257
What to do
- Check motor connection wires. p. 257
- Check auto‑tuning input data. p. 257
- Check auto‑tuning input data (22‑02). Check the inverter’s capacity. p. 257
Before you service the product, read the safety instructions in the manual p. 252.
If 09 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact TECO service.
This page summarises what the manufacturer’s manual says about 09; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with TECO. Found a mistake? Report an error.