A0511 indicates Motor I²T over‑temperature when there is motor overload or when work time is too long during the load's work‑stop cycle. The manual's first action is: “Regardless of the over‑temperature type, check the following: 1. The load’s work/stop cycle must be correct.”
- Model
- Siemens MICROMASTER 430
- Display shows
- Motor I²T over‑temperature (A0511)
- Type
- Alarm code
- Source
- Manual p. 88
What A0511 means
Motor I²T over‑temperature p. 88
Common causes
What to do
- Regardless of the over‑temperature type, check the following: 1. The load’s work/stop cycle must be correct. p. 88
- 2. The motor over‑temperature parameters (P0626‑P0628) must be correct. p. 88
- 3. The motor temperature alarm level (P0604) must match. If P0601 = 0 or 1, check the following: • Is the name‑plate data correct (if not performing fast tuning) • Accurate equivalent‑circuit data can be obtained via automatic motor‑parameter detection (P1910 = 1) • Is the motor weight (P0344) reliable; modify if necessary • If the motor is not a Siemens standard motor, adjust the over‑temperature standard values using parameters P0626, P0627, P0628. If P0601 = 2, check the following: • Is the temperature value shown by r0035 reliable • Is the sensor a KTY 84 (other sensors are not supported). p. 88
Before you service the product, read the safety instructions in the manual p. 7.
If A0511 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about A0511; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.