Siemens MICROMASTER 430 Error A0504: Inverter over‑temperature

Siemens MICROMASTER 430 · taken from the manufacturer’s manual, pages cited

Alarm codeA0504

A0504 indicates Inverter over‑temperature when the inverter heatsink temperature (P0614) exceeds the alarm level, which will cause the modulation‑pulse switching frequency and/or the output frequency to decrease (depending on P0610 parameterization). The manual's first action is: “1. Ambient temperature must be within the specified range.”

Model
Siemens MICROMASTER 430
Display shows
Inverter over‑temperature (A0504)
Type
Alarm code
Source
Manual p. 88

What A0504 means

Inverter over‑temperature p. 88

Common causes

  • The inverter heatsink temperature (P0614) exceeds the alarm level, which will cause the modulation‑pulse switching frequency and/or the output frequency to decrease (depending on P0610 parameterization). p. 88

What to do

  1. 1. Ambient temperature must be within the specified range. p. 88
  2. 2. Load condition and the work‑stop cycle time must be appropriate. p. 88
  3. 3. The fan must be running when the inverter is operating. p. 88
  4. 4. Pulse frequency (P1800) must be set to its default value. p. 88

Before you service the product, read the safety instructions in the manual p. 7.

If A0504 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about A0504; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.