Siemens MICROMASTER 430 Error A0505: Inverter I²T over‑temperature

Siemens MICROMASTER 430 · taken from the manufacturer’s manual, pages cited

Alarm codeA0505

A0505 indicates Inverter I²T over‑temperature when parameterized (P0290) and the alarm level (P0294) is exceeded, causing the output frequency and/or pulse frequency to be reduced. The manual's first action is: “1. Verify that the work‑stop cycle operating time is within the specified range.”

Model
Siemens MICROMASTER 430
Display shows
Inverter I²T over‑temperature (A0505)
Type
Alarm code
Source
Manual p. 88

What A0505 means

Inverter I²T over‑temperature p. 88

Common causes

  • If parameterized (P0290), when the alarm level (P0294) is exceeded, the output frequency and/or pulse frequency will be reduced. p. 88

What to do

  1. 1. Verify that the work‑stop cycle operating time is within the specified range. p. 88
  2. 2. Motor power (P0307) must match the inverter power. p. 88

Before you service the product, read the safety instructions in the manual p. 7.

If A0505 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about A0505; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.