Fault codeF07810
No rated data are stored in the power unit EEPROM, requiring replacement or customer service contact. The manual's first action is: “Replace the power unit or inform Siemens Customer Service.”
- Model
- Siemens G120C
- Display shows
- Drive: Power unit EEPROM without rated data (F07810)
- Type
- Fault code
- Source
- Manual p. 709
What F07810 means
Drive: Power unit EEPROM without rated data p. 709
Common causes
- No rated data are stored in the power unit EEPROM. p. 709
- See also: p0205 (Power unit application), r0206 (Rated power unit power), r0207 (Rated power unit current), r0208 (Rated power line supply voltage), r0209 (Power unit maximum current) p. 709
What to do
- Replace the power unit or inform Siemens Customer Service. p. 709
Before you service the product, read the safety instructions in the manual p. 4.
If F07810 is still not resolved
This page summarises what the manufacturer’s manual says about F07810; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.