Siemens G120C Error F07016: Drive: Motor temperature sensor fault

Siemens G120C drive · taken from the manufacturer’s manual, pages cited

Fault codeF07016

The motor temperature sensor has failed due to wire breakage or disconnection exceeding resistance thresholds. The manual lists no action for this code.

Model
Siemens G120C
Display shows
Drive: Motor temperature sensor fault (F07016)
Type
Fault code
Source
Manual p. 699

What F07016 means

Drive: Motor temperature sensor fault p. 699

Common causes

  • An error was detected when evaluating the temperature sensor set in p0601. p. 699
  • Possible causes: p. 699
  • - wire breakage or sensor not connected (KTY: R > 2120 Ohm, PT1000: R > 2120 Ohm). p. 699
  • - measured resistance too low (PTC: R < 20 Ohm , KTY: R < 50 Ohm, PT1000: R < 603 Ohm). p. 699
  • If alarm A0715 is present, the time in p0607 is started. If the fault is still present after this time has expired, then fault F07016 is output; however, at the earliest, 50 ms after alarm A0715. p. 699

If F07016 is still not resolved

  • contact service / dealer p. 4
    “Warning concept This Manual contains information which you must observe to ensure your own personal safety as well as to avoid material damage.”
  • contact service / dealer p. 12
    “WARNING Danger to life if the safety instructions and residual risks are not observed”

This page summarises what the manufacturer’s manual says about F07016; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.