Fault codeF07016
The motor temperature sensor has failed due to wire breakage or disconnection exceeding resistance thresholds. The manual lists no action for this code.
- Model
- Siemens G120C
- Display shows
- Drive: Motor temperature sensor fault (F07016)
- Type
- Fault code
- Source
- Manual p. 699
What F07016 means
Drive: Motor temperature sensor fault p. 699
Common causes
- An error was detected when evaluating the temperature sensor set in p0601. p. 699
- Possible causes: p. 699
- - wire breakage or sensor not connected (KTY: R > 2120 Ohm, PT1000: R > 2120 Ohm). p. 699
- - measured resistance too low (PTC: R < 20 Ohm , KTY: R < 50 Ohm, PT1000: R < 603 Ohm). p. 699
- If alarm A0715 is present, the time in p0607 is started. If the fault is still present after this time has expired, then fault F07016 is output; however, at the earliest, 50 ms after alarm A0715. p. 699
If F07016 is still not resolved
This page summarises what the manufacturer’s manual says about F07016; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.