Fault codeA07910
The motor temperature or model 2 temperature has exceeded the alarm threshold, triggering a response based on parameterized settings. The manual lists no action for this code.
- Model
- Siemens G120C
- Display shows
- Drive: Motor overtemperature (A07910)
- Type
- Fault code
- Source
- Manual p. 712
What A07910 means
Drive: Motor overtemperature p. 712
Common causes
- The measured motor temperature or the temperature of the motor temperature model 2 has exceeded the alarm threshold (p0604). The response parameterized in p0610 becomes active. p. 712
- PTC or bimetallic NC contact: The response threshold of 1650 Ohm was exceeded or the NC contact opened. p. 712
- Alarm value (r2124, interpret decimal): p. 712
- 11: No output current reduction. p. 712
- 12: Output current reduction active. p. 712
If A07910 is still not resolved
This page summarises what the manufacturer’s manual says about A07910; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.