Schneider Electric ATV212 Error DP3: [Overvoltage during constant speed]

Schneider Electric ATV212 · taken from the manufacturer’s manual, pages cited

Fault codeDP3

Input voltage fluctuates abnormally, supply network exceeds 200 kVA, or power factor capacitor switching. The manual's first action is: “Install a line reactor.”

Model
Schneider Electric ATV212
Display shows
[Overvoltage during constant speed] (DP3)
Type
Fault code
Source
Manual p. 154

What DP3 means

[Overvoltage during constant speed] p. 154

Common causes

  • Input voltage fluctuates abnormally. p. 154
  • Supply network exceeds 200 kVA. p. 154
  • Power factor capacitor switching. p. 154
  • SCR switching on the supply network. p. 154
  • The inverter is regenerating – the load causes the motor to run at a frequency higher than the inverter’s output frequency. p. 154
  • Output phase fault of the same type. p. 154

What to do

  1. Install a line reactor. p. 154
  2. Check the input and output circuits for phase faults and correct them. p. 154
  3. Output phase fault of the same type. p. 154

Before you service the product, read the safety instructions in the manual p. 5.

If DP3 is still not resolved

  • 与当地的 Schneider Electric 代表联系 p. 7
    “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”

This page summarises what the manufacturer’s manual says about DP3; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.