Fault codeDP3
Input voltage fluctuates abnormally, supply network exceeds 200 kVA, or power factor capacitor switching. The manual's first action is: “Install a line reactor.”
- Model
- Schneider Electric ATV212
- Display shows
- [Overvoltage during constant speed] (DP3)
- Type
- Fault code
- Source
- Manual p. 154
What DP3 means
[Overvoltage during constant speed] p. 154
Common causes
- Input voltage fluctuates abnormally. p. 154
- Supply network exceeds 200 kVA. p. 154
- Power factor capacitor switching. p. 154
- SCR switching on the supply network. p. 154
- The inverter is regenerating – the load causes the motor to run at a frequency higher than the inverter’s output frequency. p. 154
- Output phase fault of the same type. p. 154
What to do
- Install a line reactor. p. 154
- Check the input and output circuits for phase faults and correct them. p. 154
- Output phase fault of the same type. p. 154
Before you service the product, read the safety instructions in the manual p. 5.
If DP3 is still not resolved
- 与当地的 Schneider Electric 代表联系 p. 7 “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”
This page summarises what the manufacturer’s manual says about DP3; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.