Schneider Electric ATV212 Error DP2: [Overvoltage during deceleration]

Schneider Electric ATV212 · taken from the manufacturer’s manual, pages cited

Fault codeDP2

Deceleration time is too short, inertial load, or input voltage fluctuates abnormally. The manual's first action is: “Increase the deceleration time parameter (DEC or F501).”

Model
Schneider Electric ATV212
Display shows
[Overvoltage during deceleration] (DP2)
Type
Fault code
Source
Manual p. 154

What DP2 means

[Overvoltage during deceleration] p. 154

Common causes

  • Deceleration time is too short. p. 154
  • Inertial load. p. 154
  • Input voltage fluctuates abnormally. p. 154
  • Supply network exceeds 200 kVA. p. 154
  • Power factor capacitor switching. p. 154
  • SCR switching on the supply network. p. 154
  • The inverter is starting a rotating load. p. 154
  • Output phase fault of the same type. p. 154

What to do

  1. Increase the deceleration time parameter (DEC or F501). p. 154
  2. Enable parameter F305. p. 154
  3. Install a line reactor. p. 154
  4. Check the input and output circuits for phase faults and correct them. p. 154
  5. Enable flywheel start, parameter F301. p. 154
  6. The inverter is starting a rotating load. p. 154
  7. Output phase fault of the same type. p. 154

Before you service the product, read the safety instructions in the manual p. 5.

If DP2 is still not resolved

  • 与当地的 Schneider Electric 代表联系 p. 7
    “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”

This page summarises what the manufacturer’s manual says about DP2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.