Schneider Electric ATV212 Error DP1: [Overvoltage during acceleration]

Schneider Electric ATV212 · taken from the manufacturer’s manual, pages cited

Fault codeDP1

Input voltage fluctuates abnormally, supply network exceeds 200 kVA, or power factor compensation capacitor switching. The manual's first action is: “Install a line reactor.”

Model
Schneider Electric ATV212
Display shows
[Overvoltage during acceleration] (DP1)
Type
Fault code
Source
Manual p. 154

What DP1 means

[Overvoltage during acceleration] p. 154

Common causes

  • Input voltage fluctuates abnormally. p. 154
  • Supply network exceeds 200 kVA. p. 154
  • Power factor compensation capacitor switching. p. 154
  • SCR switching on the power grid. p. 154
  • The inverter is starting a rotating load. p. 154
  • Output phase fault of the same type. p. 154

What to do

  1. Install a line reactor. p. 154
  2. Enable flywheel start, parameter F301. p. 154
  3. Set parameter F302 to 2. p. 154
  4. Identify the cause of missing output phase (e.g., poor connection, output open circuit, or motor winding open) and correct it. p. 154
  5. The inverter is starting a rotating load. p. 154
  6. Output phase fault of the same type. p. 154

Before you service the product, read the safety instructions in the manual p. 5.

If DP1 is still not resolved

  • 与当地的 Schneider Electric 代表联系 p. 7
    “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”

This page summarises what the manufacturer’s manual says about DP1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.