Fault codeDH
Inverter cooling fan is not operating, ambient temperature is too high, or enclosure ventilation openings are blocked. The manual's first action is: “After cooling, reset the inverter fault and restart operation.”
- Model
- Schneider Electric ATV212
- Display shows
- [Inverter Overheat] (DH)
- Type
- Fault code
- Source
- Manual p. 154
What DH means
[Inverter Overheat] p. 154
Common causes
- Inverter cooling fan is not operating. p. 154
- Ambient temperature is too high. p. 154
- Enclosure ventilation openings are blocked. p. 154
- A heat source is too close to the inverter. p. 154
- Inverter heatsink temperature sensor is malfunctioning. p. 154
What to do
- After cooling, reset the inverter fault and restart operation. p. 154
- Increase free space around the inverter and remove any heat sources near it to lower ambient temperature. p. 154
- Check fan operation. p. 154
Before you service the product, read the safety instructions in the manual p. 5.
If DH is still not resolved
- 与当地的 Schneider Electric 代表联系 p. 7 “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”
This page summarises what the manufacturer’s manual says about DH; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.