Internal fault is triggered by short-circuit on the 10 V power supply or internal failure. The manual's first action is: “Check the circuits connected to the 10 V.”
- Model
- Schneider Electric ATV 31H
- Display shows
- Internal fault (InF)
- Type
- Fault code
- Source
- Manual p. 92
What InF means
Internal fault p. 92
Common causes
What to do
- Check the circuits connected to the 10 V. p. 92
- Check the wiring of inputs Al1 and Al2 and the connection to the RJ45 connector. p. 92
- Check the environment (electromagnetic compatibility). p. 92
- Replace the drive. p. 92
Before you service the product, read the safety instructions in the manual p. 56.
If InF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about InF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.