Schneider Electric ATV 31H Error InF: Internal fault

Variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeInF

Internal fault is triggered by short-circuit on the 10 V power supply or internal failure. The manual's first action is: “Check the circuits connected to the 10 V.”

Model
Schneider Electric ATV 31H
Display shows
Internal fault (InF)
Type
Fault code
Source
Manual p. 92

What InF means

Internal fault p. 92

Common causes

  • Short-circuit on the 10 V power supply p. 92
  • Internal fault p. 92

What to do

  1. Check the circuits connected to the 10 V. p. 92
  2. Check the wiring of inputs Al1 and Al2 and the connection to the RJ45 connector. p. 92
  3. Check the environment (electromagnetic compatibility). p. 92
  4. Replace the drive. p. 92

Before you service the product, read the safety instructions in the manual p. 56.

If InF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about InF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.