Schneider Electric ATV 31H Error DLF: Motor overload

Variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeDLF

Motor overload is triggered by excessive motor current or incorrect rSC parameter value. The manual's first action is: “Check the ItH setting (motor thermal protection) (page 20), check the motor load. Wait for the drive to cool down before restarting.”

Model
Schneider Electric ATV 31H
Display shows
Motor overload (DLF)
Type
Fault code
Source
Manual p. 93

What DLF means

Motor overload p. 93

Common causes

  • Triggered by excessive motor current p. 93
  • Incorrect value of parameter rSC p. 93

What to do

  1. Check the ItH setting (motor thermal protection) (page 20), check the motor load. Wait for the drive to cool down before restarting. p. 93
  2. Measure rSC again (page 24). p. 93

Before you service the product, read the safety instructions in the manual p. 56.

If DLF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about DLF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.