Schneider Electric ATV 31H Error bLF: Brake sequence

Variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codebLF

Brake sequence occurs when brake release current is not reached or when brake engage frequency is not adjusted while brake logic is assigned. The manual's first action is: “Check the drive/motor connection.”

Model
Schneider Electric ATV 31H
Display shows
Brake sequence (bLF)
Type
Fault code
Source
Manual p. 92

What bLF means

Brake sequence p. 92

Common causes

  • Brake release current not reached p. 92
  • Brake engage frequency bEn = nO (not adjusted) when brake logic bLC is assigned. p. 92

What to do

  1. Check the drive/motor connection. p. 92
  2. Check the motor windings. p. 92
  3. Check the lbr setting in the FU n- menu (see page 60). p. 92
  4. Carry out the recommended adjustment of bEn (see pages 59 and 60). p. 92

Before you service the product, read the safety instructions in the manual p. 56.

If bLF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about bLF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.