OBF on the Schneider Altivar 12 is listed in the manual as: Overbraking. The manual's first action is: “• Increase the deceleration time • Install a module unit with a braking resistor if necessary • Check the line supply voltage, to be sure that it is under the maximum acceptable (20% over maximum line supply during run status)”
- Model
- Schneider Altivar 12
- Display shows
- Overbraking (OBF)
- Type
- Fault code
- Source
- Manual p. 109
What OBF means
Overbraking p. 109
Common causes
- • Braking too sudden or driving load too high p. 109
What to do
- • Increase the deceleration time • Install a module unit with a braking resistor if necessary • Check the line supply voltage, to be sure that it is under the maximum acceptable (20% over maximum line supply during run status) p. 109
Before you service the product, read the safety instructions in the manual p. 4.
If OBF is still not resolved
- contact your local Schneider Electric representative p. 5 “contact your local Schneider Electric representative. Do not repair or operate the drive.”
This page summarises what the manufacturer’s manual says about OBF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.