Fault codePHF
PHF on the Schneider Altivar 12 is listed in the manual as: Input phase loss. The manual's first action is: “Check the power connection and the fuses.”
- Model
- Schneider Altivar 12
- Display shows
- Input phase loss (PHF)
- Type
- Fault code
- Source
- Manual p. 110
What PHF means
Input phase loss p. 110
Common causes
- Drive incorrectly supplied or a fuse blown p. 110
- Failure of one phase p. 110
- 3-phase ATV12 used on a single-phase line supply p. 110
- Unbalanced load p. 110
- This protection only operates with the drive on load p. 110
What to do
- Check the power connection and the fuses. p. 110
- Use a 3-phase line supply. p. 110
- Disable the fault by setting Input Phase loss detection IPL page 94 = 0. p. 110
Before you service the product, read the safety instructions in the manual p. 4.
If PHF is still not resolved
- contact your local Schneider Electric representative p. 5 “contact your local Schneider Electric representative. Do not repair or operate the drive.”
This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.