Schneider Altivar 12 Error PHF: Input phase loss

Altivar 12 variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codePHF

PHF on the Schneider Altivar 12 is listed in the manual as: Input phase loss. The manual's first action is: “Check the power connection and the fuses.”

Model
Schneider Altivar 12
Display shows
Input phase loss (PHF)
Type
Fault code
Source
Manual p. 110

What PHF means

Input phase loss p. 110

Common causes

  • Drive incorrectly supplied or a fuse blown p. 110
  • Failure of one phase p. 110
  • 3-phase ATV12 used on a single-phase line supply p. 110
  • Unbalanced load p. 110
  • This protection only operates with the drive on load p. 110

What to do

  1. Check the power connection and the fuses. p. 110
  2. Use a 3-phase line supply. p. 110
  3. Disable the fault by setting Input Phase loss detection IPL page 94 = 0. p. 110

Before you service the product, read the safety instructions in the manual p. 4.

If PHF is still not resolved

  • contact your local Schneider Electric representative p. 5
    “contact your local Schneider Electric representative. Do not repair or operate the drive.”

This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.