Fault codeSCF1

SCF1 on the Schneider Altivar 12 is listed in the manual as: Motor short circuit. The manual's first action is: “Check the cables connecting the drive to the motor, and the motor insulation”

Model
Schneider Altivar 12
Display shows
Motor short circuit (SCF1)
Type
Fault code
Source
Manual p. 108

What SCF1 means

Motor short circuit p. 108

Common causes

  • Short-circuit or grounding at the drive output p. 108
  • Ground fault during running status p. 108
  • Commutation of motors during running status p. 108
  • Significant current leakage to ground if several motors are connected in parallel p. 108

What to do

  1. Check the cables connecting the drive to the motor, and the motor insulation p. 108
  2. Connect motor chokes p. 108

Before you service the product, read the safety instructions in the manual p. 4.

If SCF1 is still not resolved

  • contact your local Schneider Electric representative p. 5
    “contact your local Schneider Electric representative. Do not repair or operate the drive.”

This page summarises what the manufacturer’s manual says about SCF1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.