Fault codebF
bF on the Schneider Altivar 12 is listed in the manual as: Auto-tuning. The manual's first action is: “Check that the motor/drive are compatible”
- Model
- Schneider Altivar 12
- Display shows
- Auto-tuning (bF)
- Type
- Fault code
- Source
- Manual p. 108
What bF means
Auto-tuning p. 108
Common causes
- Motor not connected to the drive p. 108
- One motor phase loss p. 108
- Special motor p. 108
- Motor is rotating (being driven by the load, for example) p. 108
What to do
- Check that the motor/drive are compatible p. 108
- Check that the motor is present during auto-tuning p. 108
- If an output contactor is being used, close it during auto-tuning p. 108
- Check that the motor is completely stopped p. 108
Before you service the product, read the safety instructions in the manual p. 4.
If bF is still not resolved
- contact your local Schneider Electric representative p. 5 “contact your local Schneider Electric representative. Do not repair or operate the drive.”
This page summarises what the manufacturer’s manual says about bF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.