Fault codeSCF3
SCF3 on the Schneider Altivar 12 is listed in the manual as: Ground short circuit. The manual's first action is: “Check the cables connecting the drive to the motor, and the motor insulation”
- Model
- Schneider Altivar 12
- Display shows
- Ground short circuit (SCF3)
- Type
- Fault code
- Source
- Manual p. 108
What SCF3 means
Ground short circuit p. 108
Common causes
- Short-circuit or grounding at the drive output p. 108
- Ground fault during running status p. 108
- Commutation of motors during running status p. 108
- Significant current leakage to ground if several motors are connected in parallel p. 108
What to do
- Check the cables connecting the drive to the motor, and the motor insulation p. 108
- Connect motor chokes p. 108
Before you service the product, read the safety instructions in the manual p. 4.
If SCF3 is still not resolved
- contact your local Schneider Electric representative p. 5 “contact your local Schneider Electric representative. Do not repair or operate the drive.”
This page summarises what the manufacturer’s manual says about SCF3; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.