User fault routine executed at power-up and bit S:1/3 was not cleared after the routine. The manual's first action is: “• Either reset bit S:1/3 if this is consistent with the application requirements, and change the mode back to RUN, or • clear S:1/3, the Major Error Halted bit, before the end of the User Fault Routine.”
- Model
- Rockwell Automation MicroLogix 1400
- Display shows
- STARTUP PROTECTION FAULT (0016)
- Type
- Error code
- Source
- Manual p. 402
What 0016 means
STARTUP PROTECTION FAULT p. 402
Common causes
- The user fault routine was executed at power-up, before the main ladder program. Bit S:1/3 (Major Error Halted) was not cleared at the end of the User Fault Routine. The User Fault Routine ran because bit S:1/3 was set at power-up. p. 402
What to do
- • Either reset bit S:1/3 if this is consistent with the application requirements, and change the mode back to RUN, or • clear S:1/3, the Major Error Halted bit, before the end of the User Fault Routine. p. 402
Before you service the product, read the safety instructions in the manual p. 274.
If 0016 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Rockwell Automation service.
This page summarises what the manufacturer’s manual says about 0016; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Rockwell Automation. Found a mistake? Report an error.