Mitsubishi Electric MDS-C1 Series Error 73: Over-regeneration

AC Servo/Spindle · taken from the manufacturer’s manual, pages cited

Error code73

Over-regeneration alarm triggers when regenerative resistor overload exceeds 100% during motor deceleration. The manual's first action is: “PR”

Model
Mitsubishi Electric MDS-C1 Series
Display shows
Over-regeneration (73)
Type
Error code
Source
Manual p. 312

What 73 means

Over-regeneration p. 312

Common causes

  • The over-regeneration detection level exceeded 100%. The regenerative resistor is in the overload state. p. 312
  • The regenerative load display increases each time the motor decelerates, and the alarm occurs. p. 312
  • The regenerative load display increases each time the motor decelerates, but the alarm does not occur when the operation mode is eased. p. 312
  • The setting is incorrect. p. 312
  • The setting is correct. p. 312
  • The regenerative resistor is abnormal. p. 312
  • There is no problem. p. 312

What to do

  1. PR p. 312
  2. Check whether the state is affected by power fluctuation, grounding or noise. If there is no problem, replace the unit. p. 312
  3. A-CR : Investigate item 2. C1-CV : Ease the operation mode. p. 312
  4. Correctly set. (Refer to the section for alarm No. 6D.) p. 312
  5. Investigate item 3. p. 312
  6. Replace the regenerative resistor. p. 312
  7. Investigate item 4. p. 312

Before you service the product, read the safety instructions in the manual p. 4.

If 73 is still not resolved

  • contact service / dealer p. 5
    “Wiring, maintenance and inspection work must be done by a qualified technician.”

This page summarises what the manufacturer’s manual says about 73; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Mitsubishi Electric. Found a mistake? Report an error.