ABB ACS850 Error 0031: SAFE TORQUE OFF (0xFF7A)

ABB ACS850 · taken from the manufacturer’s manual, pages cited

Fault code0031

The SAFE TORQUE OFF code indicates the Safe Torque Off function is activated when the safety circuit signal connected to the XSTO connector is lost during start-up, operation, or when the inverter is stopped. The manual's first action is: “Check the safety circuit connections. For more information, refer to the appropriate inverter hardware manual and the Application Guide – Safe Torque Off for ACSM1, ACS850, and ACQ810 Inverters (3AFE68929814 [English]).”

Model
ABB ACS850
Display shows
SAFE TORQUE OFF (0xFF7A) (0031)
Type
Fault code
Source
Manual p. 293

What 0031 means

SAFE TORQUE OFF (0xFF7A) p. 293

Common causes

  • Safe Torque Off function is activated, i.e., during start-up or operation, or when the inverter is stopped, the safety circuit signal connected to the XSTO connector is lost, and parameter 30.07 STO diagnostic is set to Fault. p. 293

What to do

  1. Check the safety circuit connections. For more information, refer to the appropriate inverter hardware manual and the Application Guide – Safe Torque Off for ACSM1, ACS850, and ACQ810 Inverters (3AFE68929814 [English]). p. 293

Before you service the product, read the safety instructions in the manual p. 179.

If 0031 is still not resolved

  • 请联系当地的 ABB 代表 p. 296
    “请联系当地的 ABB 代表”