Start here

SOYAL AR-401 Programmable Logic Controller Operation Manual
The SOYAL AR-401 is a Programmable Logic Controller (PLC) designed for smart building applications. It features a built-in HTTP server that allows users to perform programming directly via a web browser without the need for a human-machine interface (HMI). The device supports standard Modbus-TCP control syntax for all IO, making it suitable for integration with SCADA systems or SOYAL 701ClientSQL. This manual is written in Chinese.
Read onlineSOYAL AR-401 specifications
| Communication | RS-485 |
|---|---|
| Baud rate | 4800/9600/19200 bps (N, 8, 1) |
| Relay outputs | 16 Form C |
| N.O./N.C. selection | Via jumper |
| COM terminals | 16 COM dispatched to 16 relays |
| Contact rating | AC 110 V @ 0.6 A; DC 24 V @ 2 A |
| LED indicators | Power, Tx/Rx, Relay On/Off |
| Dimensions | 180 x 231 x 62 mm |
| Weight | 1,780 ± 10 g |
| Housing material | Metal |
| Watchdog timer | Built-in |
| Elevator control baud rate | 4800 bps |
Source: SOYAL Access Control System AR-401RO16B Relay Output Module Contents & Specification
All SOYAL AR-401 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What communication interface does the AR-401RO16B use?
It uses RS-485 communication.
From: SOYAL Access Control System AR-401RO16B Relay Output Module Contents & Specification
How many relay outputs does the AR-401RO16B provide?
It provides 16 Form C relay outputs.
From: SOYAL Access Control System AR-401RO16B Relay Output Module Contents & Specification
Why is the CNTInc count incorrect?
You must select edge trigger conditions (ADi or ^Di); selecting other conditions may cause count skipping.
From: SOYAL AR-401 Programmable Logic Controller Operation Manual
Why is the Timer always 0 after triggering?
The Timer starts counting after triggering and returns to zero when the trigger stops; check the time during the trigger for accuracy.
From: SOYAL AR-401 Programmable Logic Controller Operation Manual
What is the Node ID setting for elevator control?
For elevator control, the baud rate should be set to 4800bps and DIP SW5 switched to ON.
Which models is the AR-401RO16B compatible with?
It applies to models including AR-721H, AR-321H, AR-725H, AR-727H, AR-327H, AR-757H, AR-821EF, AR-829E, and AR-725E.