Phonetics SCADA 3000 UIM-2 Universal Input Module User's Manual

Phonetics SCADA 3000 UIM-2 Universal Input Module User's Manual

User Manual 19 pages · 146 KB · EN

The SCADA 3000 Universal Input Module is an optional component designed to interface with various sensors and transducers. It features eight channels capable of handling Normally Open/Normally Closed dry contacts, digital logic, run time accumulation, 0-5V analog signals, 4-20mA current loops, and 10K thermistors for temperature measurement in both Celsius and Fahrenheit.

Read online

SCADA 3000 specifications

LED Indicators8 programmable LED indicators
LED Typebi-color (red/amber)
Enclosure Size1/8 DIN enclosure
Operating Voltage10-15VDC
Power Consumption1.5 Watts
Operating Temperature0°C to 70°C (32 °F to 158 °F)
Max Modules per Bus15 modules
Max Distance2000'

Source: Phonetics SCADA 3000 Annunciator Module User Manual

All SCADA 3000 documents by type

Questions answered in these manuals

How many modules can be connected to the main unit?

Up to 15 modules can be connected using the high-speed serial communications bus.

From: Phonetics SCADA 3000 Annunciator Module User Manual

What are the LED colors and what do they indicate?

The LEDs are bi-color (red/amber); red indicates an active or ON condition, while amber indicates inactive or OFF.

From: Phonetics SCADA 3000 Annunciator Module User Manual

How many relay outputs does the module have?

The module features eight latching relay outputs.

From: Phonetics SCADA 3000 Relay Output Module User Manual

What is the relay rating?

The relays are rated at 2 Amps at 125VAC.

From: Phonetics SCADA 3000 Relay Output Module User Manual

What is the operating temperature range?

The module can operate in a temperature range of 32°F to 158°F (0°C to 70°C).

From: Phonetics SCADA 3000 Analog Output Module User's Manual

What power supply voltage is required?

The module operates on a DC power supply of 10-15V.

From: Phonetics SCADA 3000 Analog Output Module User's Manual