Metrix 5550 Manuals

ManualLib has 2 documents for the Metrix 5550 (switch): 2 installation guides. Every file can be read online or downloaded as a PDF for free.

Installation Guide 2

Key facts

Brand
Metrix
Model
5550
Category
switch
Industry
Industrial
Documents
2
Languages
EN
Last added
2026-11-17

Start here

Metrix 5550 Vibralert Mechanical Vibration Switch Installation Guide and Specifications

Metrix 5550 Vibralert Mechanical Vibration Switch Installation Guide and Specifications

Installation Guide 4 pages · 199 KB · EN

The Metrix Model 5550 Vibralert is a mechanical vibration switch with an inertia-sensitive mechanism that activates a snap-action switch with SPDT output contacts when vibration exceeds an adjustable setpoint. The document describes use on low to medium speed machinery such as heat exchanger fans, cooling tower fans, reciprocating engines, and reciprocating compressors. The switch has a weatherproof housing with an optional hazardous-area rating and offers local reset plus an optional remote reset coil with startup delay.

Specifications and selection information cover a frequency range of 0 to 3600 RPM, setpoint adjustment from 0 to 100% of range, full-scale ranges of 5 g, 2 g, and 10 g, and contact ratings. The document also includes how-to-order tables, dimensions, wiring diagrams, typical installation diagrams, installation instructions, setpoint adjustment procedures, and electrical reset/startup lockout information.

Read online

Metrix 5550 specifications

FunctionArmature mechanism trips on high vibration and operates snap-action switch(es).
Frequency range0 to 3600 RPM
Setpoint adjustment0 to 100% of range; external adjustment
Full-scale vibration ranges5 g, 2 g, or 10 g
ResetLocal reset; optional remote reset electrical coil
Start delay20-30 seconds with reset coil voltage at startup
Temperature limit-40° to +70°C (-40° to +158°F)
EnclosureCast aluminum
Environmental ratingNEMA 4, IP 65, and CE mark
Switch contact rating15 A at 125 or 480 Vac; 1/8 hp at 125 Vac; 1/4 hp at 250 Vac; 1/2 A at 125 Vdc; 1/4 A at 250 Vdc

Source: Metrix 5550 Vibralert Mechanical Vibration Switch Installation Guide and Specifications

All Metrix 5550 documents by type

Questions answered in these manuals

What happens when vibration exceeds the adjustable setpoint?

An inertia-sensitive mechanism activates a snap-action switch with SPDT output contacts.

From: Metrix 5550 Vibralert Mechanical Vibration Switch Installation Guide and Specifications

What is the frequency range of the Model 5550?

The frequency range is 0 to 3600 RPM.

From: Metrix 5550 Vibralert Mechanical Vibration Switch Installation Guide and Specifications

How is the setpoint adjusted on the Metrix 5550?

Turn the set screw on the cover clockwise to increase the setpoint and counterclockwise to decrease it; about 1/8 turn equals about 1 g.

From: Metrix 5550 and 5550G Mechanical Vibration Switch Hazardous Area Installation Manual

How long can startup lockout last?

Up to 30 seconds, or as long as voltage is continuously applied, whichever is shorter.

From: Metrix 5550 and 5550G Mechanical Vibration Switch Hazardous Area Installation Manual