Watts fixture carriers guide covering water closet, lavatory, urinal, water cooler and service sink carriers, selection and installation.
This Watts fixture carriers guide includes a pictorial index, product recommendations, water closet carrier matching, battery setup, stud and nipple adjustment, floor anchoring, thin-wall setup, commonly specified options and typical installations.
It also covers lavatory, urinal, water cooler and service sink carriers, with rough-in dimensions and installation details for commercial wall-hung fixtures.
| Closet nipple extension beyond finished wall | 5/16 in |
|---|---|
| Fixture stud extension beyond finished wall | 2-1/4 in |
| Nipple position formula | A = B - 7/16 in |
| Stud position formula | X = Y + 5/8 in |
| Carrier floor anchoring | Minimum 1/2 in diameter lag bolts |
| Standard bowl rim height | 15 in from floor |
| Handicapped bowl rim height | 18 in from floor |
| Fixture spacing in batteries | 36 in between fixtures |
| Maximum fixtures in a battery | Up to 10 fixtures |
| Auxiliary support threshold | When X dimension exceeds 18 in |
| Extended coupling standard length | 24 in |
The closet nipple is usually set 5/16 inch beyond the face of the finished wall.
Closet carriers must be anchored with minimum 1/2 inch diameter lag bolts.
Batteries may be constructed with up to 10 fixtures when a stack fitting is used in one of the center positions.
It should be used when the X dimension exceeds 18 inches.