Watts EVO/6B Normally Closed Manual Reset Gas Solenoid Valve Installation Manual

WattsWater.eu Series EVO - EVO/6B Normally closed manual reset solenoid valves for gas Installation manual Manuale di Installazione e Uso Installation and Operation Manual Manuel d’Installation et d’Utilisation Installations-und Bedienungsanleitung Manual de instalación y funcionamiento Kurulum ve Kullanım Kılavuzu


Watts EVO/6B Normally Closed Manual Reset Gas Solenoid Valve Installation Manual - cover page
Brand
Watts
Document type
User Manual
Language
English
Pages
12
File format
PDF
File size
1.4 MB
Published
17 November, 2023
Updated
17 November, 2023
MD5 checksum
2F2C43A7F4B4068F63AA2E8426DB7E77

About this manual

The Watts Series EVO EVO/6B is a normally closed manual reset solenoid valve for gas. It is held open by an electrically powered electromagnetic coil and cuts off gas flow if gas detectors reveal a leak or during a power blackout. The valve can only be reset manually when the line is powered and gas detectors show no danger.

Technical details include threaded UNI EN 10226-1 connections, maximum inlet pressure of 500 mbar (EVO) or 6 bar (EVO/6B), and an ambient temperature range of -20 to +60°C. Voltage ratings are 230V/50Hz, 24V/50Hz, or 12Vdc, with IP 65 protection, a class F coil, 11 W absorbed power, and a closing time under 1 second.

What's inside

  • Technical Specifications
  • General Features
  • Installation
  • Maintenance
  • Overall Dimensions

Specifications

Connectionsthreaded UNI EN 10226-1
Maximum inlet pressure500 mbar (EVO); 6 bar (EVO/6B)
Ambient temperature range-20 ÷ +60°C
Voltage ratings230V/50Hz, 24V/50Hz, 12Vdc (-15%+10%)
Degree of protectionIP 65
Coilclass F EN 60730
Absorbed power11 W
Closing time< 1 s

Frequently asked questions

How is the valve reset after an emergency?

Reset by pulling vertically on the knob located above the valve, only when the line is powered and gas detectors do not reveal any danger.

Does the solenoid valve require maintenance?

No. The solenoid valves do not require any maintenance; in cases of breakdown they should be overhauled and tested by the manufacturer.

What is the maximum inlet pressure for the EVO/6B model?

The maximum inlet pressure is 6 bar for EVO/6B models (500 mbar for EVO models).

Can the valve be installed in any position?

Yes. This valve can be installed in any position, though on horizontal pipes the internal duct should face upward.