Watts CC 55.1 Brass Controllable Check Valve Service Manual

The Watts brass controllable check valve CC 55.1 is a fully integrated EA check valve unit with special features, focussed on easy verification and time savings. Exchanging or cleaning a dirty or damaged check valve cartridge is now a matter of simple handling. For the DN 15 en DN 20 besides the isolation valve on the inlet side, a pressure gauge and a drain valve, a second isolation valve has been integrated into the outlet side. It prevents the drinking water installation downstream the CC 55.1 from draining during maintenance and replacement. The DN 25 with a 28 mm compression fitting has been developed specially for installation in front of a fire reel. There is already an isolation valve in front of the fire reel. For this reason the CC 55.1 DN 25 has only been given an isolation valve at the upstream side. Depending on your application, you might also order the basic model CC, a brass check valve without pressure gauge and drain valve.


Watts CC 55.1 Brass Controllable Check Valve Service Manual - cover page
Brand
Watts
Category
Industrial Supply
Document type
Service Manual
Language
English
Pages
8
File format
PDF
File size
1.4 MB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
FA786F435CC76DCA666D4DD917AE85BD

About this manual

The Watts Brass Controllable Check Valve CC 55.1 is a fully integrated check valve unit with special features for easy verification and time savings. The unit is a brass check valve with a pressure gauge and drain valve. For DN 15 and DN 20, it also has a second isolation valve at the outlet. The DN 25 version has a 28 mm compression fitting and was developed for installation in front of a fire reel. It was made in conformance with EN1717.

Installation and testing should be done by qualified personnel. Before installation, the upstream piping should be flushed. The testing procedure includes closing stop valves, opening the tap or test valve, and checking the pressure gauge for at least 30 seconds. If the pressure drops, the check valve module should be replaced.

What's inside

  • Installation of a Backflow Preventer
  • Installation and Commissioning Instructions
  • Testing Procedure
  • Technical Specifications
  • Material Specifications
  • Dimensions and Article Numbers
  • Pressure Loss Graph
  • Approvals and Standards

Specifications

Operating pressurePN 10
Nominal operating temperature65 °C
Peak temperature90 °C during 1 hour/day (gauge: max. 70 °C)
Nominal diameterDN 15, DN 20, DN 25
Connections15, 22, 28 mm Compression fittings

Frequently asked questions

What standard does the CC 55.1 conform to?

The CC 55.1 was developed in conformance with EN1717.

What is the testing procedure for the CC 55.1?

Close the outlet stop valve, close the inlet stop valve, open the tap or test valve, and check the pressure gauge for at least 30 seconds. Replace the check valve module if the pressure drops.

What is the nominal operating temperature?

The nominal operating temperature is 65 °C, and the peak temperature is 90 °C during 1 hour per day.

What is the DN25 version designed for?

The DN25 has a 28 mm compression fitting and was developed for installation in front of a fire reel. It has an isolation valve upstream because the fire reel already has one.